Description
The Omron S8JX-N01524D is a switch mode power supply with an open type configuration and a power rating of 15W. It is designed for DIN rail-mounting and has an input voltage range of 100 to 240VAC. The output voltage is 24V with a current of 0.65A and there is no built-in fan. The power supply has a weight of 250g and an efficiency of at least 68%. It is not recommended to use an inverter output with this power supply as it may result in ignition or burning. The output voltage can be adjusted within a range of -10% to 15% with a voltage adjuster, but caution should be taken to avoid damaging the load. The weight indicated is for a front-mounting, open-frame power supply. The power supply is compliant with EC Directives and safety standards within a voltage range of 100 to 240VAC.
[Configuration]Open type Power Supplies
DIN rail-mounting
[Input voltage]100 to 240VAC
(free)
[Power ratings]15W
[Output voltage/Current(VDC/A)]24V/0.65A
[Built-in fan]No
Ratings
[Input specification]100 to 240 V input
[Power ratings *1]15 W
[Efficiency]68% min.
[Input]
Voltage *2 100 to 240 VAC(allowable range: 85 to 264 VAC,80 to 370 VDC *6)
Frequency *2 50/60 Hz(47 to 450 Hz)
[Output *3]
Voltage adjustment range *4 - 10% to 15%(with V. ADJ)(48-V models: +/- 10%)
[Weight *5]250g max.
*1. When a load is connected that has a built-in DC-DC converter,
the overload protection may operate at startup and thePower Supply may not start.
*2. Do not use an Inverter output for the Power Supply.
Inverters with an output frequency of 50/60 Hz are available,
butthe rise in the internal temperature of the Power Supply may result in ignition or burning.
*3. Output characteristics: Specified at power supply output terminals.
*4. If the output voltage adjuster(V. ADJ)is turned,the voltage will increase by more than the allowable voltage range.
When adjusting the output voltage,
confirm the actual output voltage from the Power Supply and be sure thatload is not damaged.
*5. The weight indicated is for Front-mounting,Open-frame Power Supply.
*6. The range for compliance with EC Directives and safety standards(UL,EN,etc.)is 100 to 240 VAC(85 to 264 VAC).